IStarUSA IS-1800RH1UP Datasheet Page 6

  • Download
  • Add to my manuals
  • Print
  • Page
    / 10
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 5
6
AC Input AC Off AC On
T
vout_holdup
Vout
T
ac_on-delay Tpwok_low
Tsb_on-delay Tpwok_off Tpwok_off
PWOK T
pwok_on Tpwok_holdup Tsb_on-delay Tpwok_on
Tpson_pwok
+5VSB T
sb_vout Tsb_holdup
Min.>70mS
Tpson_on_delay
PSON#
AC turn 0n/off cycle PSON turn on/off cycle
Figure 2 : Turn On/Off Timing
3.4 Remote On/Off Control : PSON#
The PSON# signal is required to remotely turn on/off the power supply. PSON# is an active low signal
that turns on the +5V, +3.3V, +12V,-5V and –12V power rails. When this signal is not pulled low by
the system, or left open, the outputs (except the +5VSB and V bias) turn off. This signal is pulled to a
standby voltage by a pull-up resistor internal to the power supply.
niard/rotcelloc nepo na stpeccA epyT langiS
input from the system. Pull-up to
VSB located in power supply.
NO rewoP woL = #NOSP
FFO rewoP hgiH = #NOSP
Table 6 – PWOK Signal Characteristic
3.5 Efficiency
The efficiency is ʁ 75% at full loading condition to help reduce system power consumption at typical
system loading conditions.
.
3.6 +5VSB (Standby)
The +5VSB output is always on (+5V Standby) when AC power is applied and power switch is turned
on.
The +5VSB line is capable of delivering at a maximum of 3A for PC board circuit to operate.
4. Protection
Protection circuits inside the power supply shall cause only the power supply’s main outputs to
shutdown. If the power supply latches off due to a protection circuit tripping, either a AC cycle OFF for
15 sec, or PSON# cycle HIGH for 1 sec must be able to restart the power supply.